Covered Line ÌÇÐÄVlog´«Ã½ Alloy 6201 Aluminum Conductor
Covered AL Line ÌÇÐÄVlog´«Ã½ Weatherproof
Applications
Covered Line ÌÇÐÄVlog´«Ã½ is used primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.
Construction
Conductors are aluminum alloy 1350-H19, 6201-181, or ACSR conductors, concentrically stranded and covered for weather proofing with polyethylene, high density polyethylene (HD) or crosslinked polyethylene (XLP).
Standards
Covered Line ÌÇÐÄVlog´«Ã½ is used primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.
Construction
Conductors are aluminum alloy 1350-H19, 6201-181, or ACSR conductors, concentrically stranded and covered for weather proofing with polyethylene, high density polyethylene (HD) or crosslinked polyethylene (XLP).
Standards
- ASTM B-230 - Aluminum 1350-H19 ÌÇÐÄVlog´«Ã½ for Electrical Purposes.
- ASTM B-231 - Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR).
- ASTM B-1248 - Polyethylene Plastics Molding and Extrusion Materials.
- ASTM C-8.35 - Specifications for Weather-Resistant Polyethylene-Covered ÌÇÐÄVlog´«Ã½ and Cable.
- ICEAS-61-402
- NEMA PUB NO. WC 5-1973 - Standards Publication Thermoplastic insulated ÌÇÐÄVlog´«Ã½ and Cable for the Transmission and Distribution of Electrical Energy.
- The code words as given apply to conventional polyethylene line wire.
- For 6201 aluminum conductors diameter equivalent to ACSR construction or 1350 aluminum equivalent.
- Ampacity ratings based on 75 ºC conductor temperature, 25 ºC ambient temperature elevation - sea level. Emissivity 0.91 coefficient of absorption 0.95. Thermal resistivity of covering -3ºC-Cm2/Watt-CM. Wind speed 2ft/sec in sun.
- To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Item # |
Size
|
Strand |
Insulation
|
Outside
|
Rated
|
Weight
|
Weight
|
Ampacity
|
|---|---|---|---|---|---|---|---|---|
| Hornbeam Hornbeam/Asset/AL-Weatherproof-Line-ÌÇÐÄVlog´«Ã½.png |
Size (AWG or kcmil) N/A 4 |
Strand N/A 7/w |
Insulation Thickness (mils) N/A 30 mls |
Outside Diameter N/A .310 Inches |
Rated Breaking Strength N/A 1480 Lbs |
Weight Per (lb/1000 ft) XLP N/A 62.1 Lbs |
Weight (lb/1000 ft) Poly N/A 60.1 Lbs |
Ampacity XLP N/A 145 Amps |
| Linden Linden/Asset/AL-Weatherproof-Line-ÌÇÐÄVlog´«Ã½.png |
Size (AWG or kcmil) N/A 2 |
Strand N/A 7/w |
Insulation Thickness (mils) N/A 45 mls |
Outside Diameter N/A .406 Inches |
Rated Breaking Strength N/A 2520 Lbs |
Weight Per (lb/1000 ft) XLP N/A 96.1 Lbs |
Weight (lb/1000 ft) Poly N/A 93.3 Lbs |
Ampacity XLP N/A 190 Amps |
| Oilnut Oilnut/Asset/AL-Weatherproof-Line-ÌÇÐÄVlog´«Ã½.png |
Size (AWG or kcmil) N/A 1/0 |
Strand N/A 7/w |
Insulation Thickness (mils) N/A 60 mls |
Outside Diameter N/A .518 Inches |
Rated Breaking Strength N/A 4010 Lbs |
Weight Per (lb/1000 ft) XLP N/A 166.1 Lbs |
Weight (lb/1000 ft) Poly N/A 160.0 Lbs |
Ampacity XLP N/A 250 Amps |
| Waterash Waterash/Asset/AL-Weatherproof-Line-ÌÇÐÄVlog´«Ã½.png |
Size (AWG or kcmil) N/A 2/0 |
Strand N/A 7/w |
Insulation Thickness (mils) N/A 60 mls |
Outside Diameter N/A .567 Inches |
Rated Breaking Strength N/A 4850 Lbs |
Weight Per (lb/1000 ft) XLP N/A 203.3 Lbs |
Weight (lb/1000 ft) Poly N/A 196.4 Lbs |
Ampacity XLP N/A 290 Amps |
| Shellbark Shellbark/Asset/AL-Weatherproof-Line-ÌÇÐÄVlog´«Ã½.png |
Size (AWG or kcmil) N/A 3/0 |
Strand N/A 7/w |
Insulation Thickness (mils) N/A 60 mls |
Outside Diameter N/A .622 Inches |
Rated Breaking Strength N/A 6110 Lbs |
Weight Per (lb/1000 ft) XLP N/A 249.4 Lbs |
Weight (lb/1000 ft) Poly N/A 241.4 Lbs |
Ampacity XLP N/A 335 Amps |
| Planetree Planetree/Asset/AL-Weatherproof-Line-ÌÇÐÄVlog´«Ã½.png |
Size (AWG or kcmil) N/A 4/0 |
Strand N/A 7/w |
Insulation Thickness (mils) N/A 60 mls |
Outside Diameter N/A .683 Inches |
Rated Breaking Strength N/A 7700 Lbs |
Weight Per (lb/1000 ft) XLP N/A 307.3 Lbs |
Weight (lb/1000 ft) Poly N/A 298.1 Lbs |
Ampacity XLP N/A 385 Amps |